Tucker, DeKalb County

FIVE OAKS APARTMENTS

1200 MONTREAL RD TUCKER, GA 30084

Pool
Latest score
95
Jun 3, 2024
City
Tucker
County
DeKalb
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 3, 2024

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

13-190(a): The equipment shall be operated continuously on a 24-hour basis to obtain a minimum of 1 turnover every 6 hours. The turnover rate was observed at 80, it should be at least 188.

May 23, 2024

Permit/Opening

Score: 718 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: Yes

13-189(c)(1) - free chlorine shall be kept between 3ppm-10ppm. Observed chlorine at 1.63 ppm and again at 1.99 ppm.

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1): The pool shall be maintained with a pH level between 7.2-7.8. Observed at 6.7 and again at 8.6.

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(a): The water should be continuously chemically treated with disinfecting agent measured by simple and accurate test. Observed leak from chemical feeder in equipment room.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a): The equipment shall be operated continuously on a 24-hour basis to obtain a minimum of 1 turnover every 6 hours. The turnover rate was observed t 80, it should be at least 188.

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gpm and shall be conspicuously located. Observed two flow meters, one was not located on the return line and not working properly.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m) - rules must contain at a minimum the 12 statements in the pool code. Observed signs with missing statements.

24 - piping identified and marked

1 ptsCorrected: NoRepeat: No

13-1191(a): All valves and piping in the equipment room shall be clearly labeled. Observed some were labeled, some were not.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-189(c)(1): A D.P.D test shall measure the free chlorine residual. Observed expired chemicals in the CPO's test kit. 13-202(l): Each pool facility shall have a departmentally approved EAP. Observed no EAP.

Aug 30, 2023

Routine

Score: 746 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1) - free chlorine shall be kept between 3ppm-10ppm

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1) - depth markers must be at least 4 inches high

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-190(a) - all circulation components shall function properly

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4) - each skimmer shall have an operating weir

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m) - rules must contain at a minimum the 12 statements in the pool code

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-189(a)(5) all pools shall be kept free from dirt or debris

Jul 20, 2023

Re-inspection

Score: 884 violations

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) - equipment shall obtain minimum required one turnover every 4 hours. Minimum is 187 gpm. Observed flowmeter reading of 75 gpm

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1) - depth markers must be at least 4 inches high. Observed "FT" less than 4 inches high

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m) - rules must contain at a minimum the 12 statements in the pool code

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(I) - EACH POOL SHALL HAVE A DEPARTMENTALLY APPROVED EMERGENCY ACTION PLAN (EAP).

Jul 10, 2023

Routine

Score: 705 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(C)(1) - FREE CHLORINE SHALL BE MAINTAINED BETWEEN 3 PPM AND 10 PPM. OBSERVED FREE CHLORINE AT 0.19 PPM

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(A) - EQUIPMENT SHALL BE OPERATED TO MAINTAIN REQUIRED TURNOVER RATE.A 45,000 GALLON POOL WITH FEATURES HAS A MINIMUM TURNOVER OF 187 GPM. FLOWMETER WAS NOT WORKING

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-202(C) - POOL OPERATOR SHALL MAINTAIN AND MAKE AVAILABLE FOR INSPECTION A DAILY RECORD OF OPERATING INFORMATION INCLUDING DISINFECTANT LEVELS, PH, AND MAINTENANCE PROCEDURES. POOL SHALL BE TESTED AT LEAST TWICE DAILY

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-190(A) - ALL CIRCULATION SYSTEM COMPONENTS SHALL FUNCTION PROPERLY AND BE MAINTAINED IN A CLEAN CONDITION. SKIMMERS NEEDED TO BE CLEANED OUT AND WERE NOT WORKING

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(I) - EACH POOL SHALL HAVE A DEPARTMENTALLY APPROVED EMERGENCY ACTION PLAN (EAP). EAP ACTION PLAN COULD NOT BE FOUND

Jun 2, 2023

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.