Jun 3, 2024
Permit/Opening
19 - adequate turnover rate
13-190(a): The equipment shall be operated continuously on a 24-hour basis to obtain a minimum of 1 turnover every 6 hours. The turnover rate was observed at 80, it should be at least 188.
1200 MONTREAL RD TUCKER, GA 30084
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-190(a): The equipment shall be operated continuously on a 24-hour basis to obtain a minimum of 1 turnover every 6 hours. The turnover rate was observed at 80, it should be at least 188.
Permit/Opening
13-189(c)(1) - free chlorine shall be kept between 3ppm-10ppm. Observed chlorine at 1.63 ppm and again at 1.99 ppm.
13-189(c)(1): The pool shall be maintained with a pH level between 7.2-7.8. Observed at 6.7 and again at 8.6.
13-197(a): The water should be continuously chemically treated with disinfecting agent measured by simple and accurate test. Observed leak from chemical feeder in equipment room.
13-190(a): The equipment shall be operated continuously on a 24-hour basis to obtain a minimum of 1 turnover every 6 hours. The turnover rate was observed t 80, it should be at least 188.
13-190(a)(7): An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gpm and shall be conspicuously located. Observed two flow meters, one was not located on the return line and not working properly.
13-202(m) - rules must contain at a minimum the 12 statements in the pool code. Observed signs with missing statements.
13-1191(a): All valves and piping in the equipment room shall be clearly labeled. Observed some were labeled, some were not.
13-189(c)(1): A D.P.D test shall measure the free chlorine residual. Observed expired chemicals in the CPO's test kit. 13-202(l): Each pool facility shall have a departmentally approved EAP. Observed no EAP.
Routine
13-189(c)(1) - free chlorine shall be kept between 3ppm-10ppm
13-188(d)(1) - depth markers must be at least 4 inches high
13-190(a) - all circulation components shall function properly
13-196(a)(4) - each skimmer shall have an operating weir
13-202(m) - rules must contain at a minimum the 12 statements in the pool code
13-189(a)(5) all pools shall be kept free from dirt or debris
Re-inspection
13-190(a) - equipment shall obtain minimum required one turnover every 4 hours. Minimum is 187 gpm. Observed flowmeter reading of 75 gpm
13-188(d)(1) - depth markers must be at least 4 inches high. Observed "FT" less than 4 inches high
13-202(m) - rules must contain at a minimum the 12 statements in the pool code
13-202(I) - EACH POOL SHALL HAVE A DEPARTMENTALLY APPROVED EMERGENCY ACTION PLAN (EAP).
Routine
13-189(C)(1) - FREE CHLORINE SHALL BE MAINTAINED BETWEEN 3 PPM AND 10 PPM. OBSERVED FREE CHLORINE AT 0.19 PPM
13-190(A) - EQUIPMENT SHALL BE OPERATED TO MAINTAIN REQUIRED TURNOVER RATE.A 45,000 GALLON POOL WITH FEATURES HAS A MINIMUM TURNOVER OF 187 GPM. FLOWMETER WAS NOT WORKING
13-202(C) - POOL OPERATOR SHALL MAINTAIN AND MAKE AVAILABLE FOR INSPECTION A DAILY RECORD OF OPERATING INFORMATION INCLUDING DISINFECTANT LEVELS, PH, AND MAINTENANCE PROCEDURES. POOL SHALL BE TESTED AT LEAST TWICE DAILY
13-190(A) - ALL CIRCULATION SYSTEM COMPONENTS SHALL FUNCTION PROPERLY AND BE MAINTAINED IN A CLEAN CONDITION. SKIMMERS NEEDED TO BE CLEANED OUT AND WERE NOT WORKING
13-202(I) - EACH POOL SHALL HAVE A DEPARTMENTALLY APPROVED EMERGENCY ACTION PLAN (EAP). EAP ACTION PLAN COULD NOT BE FOUND
Permit/Opening