Apr 14, 2026
Permit/Opening
5001 CHAPEL CROSSING DOUGLASVILLE, GA 30135
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Chlorine too high. Chlorine concentrations must be between 2-10ppm
Re-inspection
Permit/Opening
Regulation: .10(5) - compliant drain cover
Observed wave suction wings on one of the main drains with broken or missing wings. Drain cover must be replaced.
Re-inspection
Observed flow meter stuck at 0ppm. CA: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute
Observed chemical log with only information from June. CA: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Observed CYA above 100ppm. CA: Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90
Observed light fixture pulled-not fit wall in pool. CA: Light fixture must ve repaired.
Routine
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH too low at below 7.0 must be between 7.2-7.8
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter stuck at 0ppm. CA: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Observed chemical log with only information from June. CA: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed CYA above 100ppm. CA: Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed hand rail on stairs loose. CA: Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Re-inspection
Dripping in pump room. Repair
Permit/Opening
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
pH too low at below 7.0 must be between 7.2-7.8
Return inlets bubbling. CA: Check for air leaks.
Boot caps missing on the far ladder. CA: Replace boot caps.
Permit/Opening
Regulation: .10(5) - compliant drain cover
Equalizer lines do not have complaint covers. VGB compliant drain covers needed on equalizer line. Some covers missing.
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone not working. Emergency phone must be operable. Needs repair/replace
Regulation: .17((1)(c) - proper disinfectant level
Chlorine too high. Chlorine concentrations must be between 2-10ppm
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed return inlets with air bubbles coming out. Indicates leak. Return inlets m
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed return inlets with air bubbles coming out. Indicates leak. Return inlets m