Lithia Springs, Douglas County

Atlanta West Campground

2420 OLD ALABAMA RD AUSTELL, GA 30168

Tourist
Latest score
94
Apr 23, 2026
City
Lithia Springs
County
Douglas
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Apr 23, 2026

Routine

Score: 942 violations

5 - sewers/sewage disposal systems/dump stations approved; properly constructed and installed; no surface discharge

Regulation: 511-6-2-.09(2) - sewers-trailer connections

5 ptsCorrected: NoRepeat: No

OBSERVED LEAK UNDER TRAILER IN LOT #52. CA: ADDRESS LEAK. Each independent trailer space shall be provided with a sewer connection not less than three inches in diameter. The design of these sewer connections shall be such that a watertight junction will be made with the trailer outlet. Each sewer connection shall be so constructed that it can be closed and when not in use shall be capped to prevent escape of odors

20 - sewers and drains maintained, connections capped

Regulation: 511-6-2-.09(2) - watertight connection

1 ptsCorrected: NoRepeat: Yes

OBSERVED SEVERAL LOTS WITHOUT SEWER CAPS. ALL SEWER MUST BE CAPPED PROPERLY. (NOTED: LOT #54, WHITE PVC PIPE AREA, DUMP STATION, LOT #7, AND OTHERS.) CA: PROPERLY COVER SEWER OPENINGS. Each independent trailer space shall be provided with a sewer connection not less than three inches in diameter. The design of these sewer connections shall be such that a watertight junction will be made with the trailer outlet. Each sewer connection shall be so constructed that it can be closed and when not in use shall be capped to prevent escape of odors

Oct 20, 2025

Routine

Score: 789 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

OBSERVED NO HOT WATER IN MENS/WOMENS RESTROOM. CA: Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

5 - sewers/sewage disposal systems/dump stations approved; properly constructed and installed; no surface discharge

Regulation: 511-6-2-.09(2) - sewers-trailer connections

5 ptsCorrected: NoRepeat: No

OBSERVED IMPROPER SEWER CONNECTIONS AT SPACE #57. OBSERVED LEAK UNDER TRAILER #59. *NOTE: SEVERAL OTHER UNMARKED SPACES NOT CONNECTED. CA: Each independent trailer space shall be provided with a sewer connection not less than three inches in diameter. The design of these sewer connections shall be such that a watertight junction will be made with the trailer outlet. Each sewer connection shall be so constructed that it can be closed and when not in use shall be capped to prevent escape of odors

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(1) - grounds graded, walkways, driveways

3 ptsCorrected: NoRepeat: No

OBSERVED TRAILER SPACES NOT MARKED CLEARLY. CA: LABEL ALL TRAILER SITES. OBSERVED ROADS FOR TRAILERS IN DISREPAIR. CA: The grounds of a tourist accommodation shall be graded to drain. Serviceable walks and driveways shall be provided

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

OBSERVED MENS/WOMENS RESTROOMS IN DISREPAIR (BROKEN TILES-COUNTERS AND SHOWERS), MISPLACED CEILING TILES, AND ETC. OBSERVED MISSING CEILING TILES AND FLOOR DRAINS. OBSERVED INOPERABLE URINALS IN MENS RESRROOM. OBSERVED SINK LEAKING IN WOMENS RESTROOM. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair. While being used by tourists, every surface of a bathtub, shower, shower enclosure, toilet and lavatory, which may come in contact with a person’s body, must be sanitized each day, unless the guest has declined regular tourist room services. If a tourist declines regular tourist room services, the tourist accommodation facility must ensure that these surfaces are cleaned and sanitized at least once per week and between tourists

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

OBSERVED VENTS NOT OPERATIONAL IN MENS/WOMENS RESTROOMS. OBSERVED ODORS IN RESTROOMS. OBSERVED MOLD ON CEILING AND SHOWER CURTAINS IN MENS/WOMENS RESTROOMS. CA: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(7) - soap available/dispensed

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Toilet tissue shall be provided in a dispenser at each toilet at all times

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

OBSERVED NO ANTI SLIP MATS IN WOMENS RESTROOMS. CA: Anti-slip tubs slip strips, appliqués, or slip-proof mats shall be provided in each bathing facility and shall be kept clean and in good repair

20 - sewers and drains maintained, connections capped

Regulation: 511-6-2-.09(2) - watertight connection

1 ptsCorrected: NoRepeat: No

OBSERVED LOT 3, 20, 53, 62, 63, 64, 10, AND OTHERS WITHOUT SEWER CAPS. ALL SEWER CAPS MUST BE COVERED. CA: Each independent trailer space shall be provided with a sewer connection not less than three inches in diameter. The design of these sewer connections shall be such that a watertight junction will be made with the trailer outlet. Each sewer connection shall be so constructed that it can be closed and when not in use shall be capped to prevent escape of odors

35 - electrical work and materials in compliance; grounded and weatherproof outlets, properly located power lines

Regulation: 511-6-2-.18(6) - eletrical supply

1 ptsCorrected: NoRepeat: No

OBSERVED MANY BROKEN/DAMAGED ELECTRICAL BOXES (SPACES: 10, 6, 17, 18, 62, AND OTHERS). CA: Grounded and weather-proof electrical outlets supplying at least one-hundred- fifteen volts shall be provided at each trailer space. Power lines shall be located underground or suspended at least eighteen feet above ground. All electrical work and materials shall comply with the applicable International Electrical Code with Georgia Amendments and local laws, ordinances, or regulations. REPAIR OR DECOMISSION ELECTRICAL BOXES.

Jun 12, 2025

Routine

Score: 8010 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

OBSERVED NO HOT WATER IN WOMENS RESTROOM. CA: Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(1) - grounds graded, walkways, driveways

3 ptsCorrected: NoRepeat: No

OBSERVED TRAILER SPACES NOT MARKED CLEARLY. CA: LABEL ALL TRAILER SITES

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

OBSERVED MENS/WOMENS RESTROOMS IN DISREPAIR (BROKEN TILES-COUNTERS AND SHOWERS), MISPLACED CEILING TILES, AND ETC. OBSERVED MISSING CEILING TILES AND FLOOR DRAINS. OBSERVED INOPERABLE URINALS IN MENS RESRROOM. OBSERVED SINK LEAKING IN WOMENS RESTROOM. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair. While being used by tourists, every surface of a bathtub, shower, shower enclosure, toilet and lavatory, which may come in contact with a person’s body, must be sanitized each day, unless the guest has declined regular tourist room services. If a tourist declines regular tourist room services, the tourist accommodation facility must ensure that these surfaces are cleaned and sanitized at least once per week and between tourists

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

OBSERVED VENTS NOT OPERATIONAL IN MENS/WOMENS RESTROOMS. OBSERVED ODORS IN RESTROOMS. OBSERVED MOLD ON CEILING AND SHOWER CURTAINS IN MENS/WOMENS RESTROOMS. CA: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(9) - toilet tissue available

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Toilet tissue shall be provided in a dispenser at each toilet at all times

31 - barrier adequate, gate locked, and installed properly; warning sign posted, procedures and log maintained

Regulation: 511-6-2-.16(2) - swimming pool barrier

2 ptsCorrected: NoRepeat: No

OBSERVED POOL BARRIER NOT IN SOUND CONDITION. CA: If a swimming pool or spa at a bed and breakfast inn cannot comply with applicable regulations, then it must be enclosed with a fence at least four feet in height with a locked gate and used only by family members. In such case, guests shall not be allowed to use swimming pool or spa. BRING POOL INTO COMPLIANCE OR LEGAL ACTION WILL BE INITIATED.

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

OBSERVED NO ANTI SLIP MATS IN MENS/WOMENS RESTROOMS. CA: Anti-slip tubs slip strips, appliqués, or slip-proof mats shall be provided in each bathing facility and shall be kept clean and in good repair

20 - sewers and drains maintained, connections capped

Regulation: 511-6-2-.09(2) - watertight connection

1 ptsCorrected: NoRepeat: No

OBSERVED LOT 12, 37, AND 53 WITHOUT SEWER CAPS. ALL SEWER CAPS MUST BE COVERED. CA: Each independent trailer space shall be provided with a sewer connection not less than three inches in diameter. The design of these sewer connections shall be such that a watertight junction will be made with the trailer outlet. Each sewer connection shall be so constructed that it can be closed and when not in use shall be capped to prevent escape of odors

30 - complies with all applicable regulations, permitted, approved operation

Regulation: 511-6-2-.16(1) - swimming pool in compliance with rules

1 ptsCorrected: NoRepeat: No

OBSERVED POOL BARRIER NOT IN COMPLIANCE. OBSERVED POOL COVER RIPPED. CA: Regulations of the Department and/ county in which govern the design, construction, operation and maintenance of swimming pools or spas shall apply to pools and spas operated in conjunction with a tourist accommodation. BRING POOL INTO COMPLIANCE OR LEGAL ACTION WILL BE INITIATED.

35 - electrical work and materials in compliance; grounded and weatherproof outlets, properly located power lines

Regulation: 511-6-2-.18(6) - eletrical supply

1 ptsCorrected: NoRepeat: No

OBSERVED MANY BROKEN/DAMAGED ELECTRICAL BOXES. CA: Grounded and weather-proof electrical outlets supplying at least one-hundred- fifteen volts shall be provided at each trailer space. Power lines shall be located underground or suspended at least eighteen feet above ground. All electrical work and materials shall comply with the applicable International Electrical Code with Georgia Amendments and local laws, ordinances, or regulations. REPAIR OR DECOMISSION ELECTRICAL BOXES.

Nov 21, 2024

Routine

Score: 7911 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

OBSERVED ONE SINK IN MENS RESTROOM WITH ONLY HOT WATER AND ONE SINK WITH ONLY COLD WATER. CA: Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(1) - grounds graded, walkways, driveways

3 ptsCorrected: NoRepeat: No

OBSERVED TRAILER SPACES NOT MARKED CLEARLY. CA: LABEL ALL TRAILER SITES

10 - permit and inspection report current and properly displayed; pic assigned

Regulation: 511-6-2-.05(7) - inspection posting

2 ptsCorrected: NoRepeat: No

OBSERVED OLD INSPECTION REPORT POSTED. CA: The most recent tourist accommodation inspection report form shall be prominently displayed in public view at all times, between five feet and seven feet from the floor and in a public area such as the registration desk, where it can be read at a distance of one foot away

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

OBSERVED MENS/WOMENS RESTROOMS IN DISREPAIR. OBSERVED MISSING CEILING TILES AND FLOOR DRAINS. OBSERVED INOPERABLE URINALS IN MENS RESRROOM. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair. While being used by tourists, every surface of a bathtub, shower, shower enclosure, toilet and lavatory, which may come in contact with a person’s body, must be sanitized each day, unless the guest has declined regular tourist room services. If a tourist declines regular tourist room services, the tourist accommodation facility must ensure that these surfaces are cleaned and sanitized at least once per week and between tourists

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

OBSERVED VENTS NOT OPERATIONAL IN RESTROOMS. OBSERVED ODORS IN RESTROOMS. CA: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(7) - soap available/dispensed

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Unused, individually wrapped soap or liquid soap dispensed from approved containers shall be provided in guest rooms. Soap furnished in public wash rooms or baths shall be dispensed from approved containers designed to preclude contamination of the contents by individual contact

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(9) - toilet tissue available

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Toilet tissue shall be provided in a dispenser at each toilet at all times

31 - barrier adequate, gate locked, and installed properly; warning sign posted, procedures and log maintained

Regulation: 511-6-2-.16(2) - swimming pool barrier

2 ptsCorrected: NoRepeat: No

OBSERVED POOL BARRIER NOT IN SOUND CONDITION. CA: If a swimming pool or spa at a bed and breakfast inn cannot comply with applicable regulations, then it must be enclosed with a fence at least four feet in height with a locked gate and used only by family members. In such case, guests shall not be allowed to use swimming pool or spa. BRING POOL INTO COMPLIANCE OR LEGAL ACTION WILL BE INITIATED.

35 - electrical work and materials in compliance; grounded and weatherproof outlets, properly located power lines

Regulation: 511-6-2-.18(6) - eletrical supply

1 ptsCorrected: NoRepeat: No

OBSERVED MANY BROKEN/DAMAGED ELECTRICAL BOXES. CA: Grounded and weather-proof electrical outlets supplying at least one-hundred- fifteen volts shall be provided at each trailer space. Power lines shall be located underground or suspended at least eighteen feet above ground. All electrical work and materials shall comply with the applicable International Electrical Code with Georgia Amendments and local laws, ordinances, or regulations. REPAIR OR DECOMISSION ELECTRICAL BOXES.

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

OBSERVED NO ANTI SLIP MATS IN MENS/WOMENS RESTROOMS. CA: Anti-slip tubs slip strips, appliqués, or slip-proof mats shall be provided in each bathing facility and shall be kept clean and in good repair

30 - complies with all applicable regulations, permitted, approved operation

Regulation: 511-6-2-.16(1) - swimming pool in compliance with rules

1 ptsCorrected: NoRepeat: No

OBSERVED POOL BARRIER NOT IN COMPLIANCE. OBSERVED POOL COVER RIPPED. CA: Regulations of the Department and/ county in which govern the design, construction, operation and maintenance of swimming pools or spas shall apply to pools and spas operated in conjunction with a tourist accommodation. BRING POOL INTO COMPLIANCE OR LEGAL ACTION WILL BE INITIATED.

Jun 24, 2024

Routine

Score: 7112 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

OBSERVED MENS AND WOMENS RESTROOMS WITHOUT HOT WATER. CA:Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

5 - sewers/sewage disposal systems/dump stations approved; properly constructed and installed; no surface discharge

Regulation: 511-6-2-.09(2) - sewers-trailer connections

5 ptsCorrected: NoRepeat: No

OBSERVED ALARM LIGHT FOR SEWAGE LIFT STATION LIT. CA: CALL FOR SERVICING/REPAIR

6 - premises free of pests and rodents; pesticide applied in accordance with laws, rules, and label

Regulation: 511-6-2-.13(1) - insect and rodent control

5 ptsCorrected: NoRepeat: No

OBSERVED SEWER FLIES AND WASPS IN MEN/WOMENS RESTROOMS. CA: Effective and appropriate measures shall be taken to eliminate the presence of rodents and flies, roaches, bed bugs, and other insects on the premises. The premises shall be kept in such condition as to prevent the attraction, harborage or feeding of insects or rodents. Restricted use pesticides, as specified in 40 CFR 152 Subpart I - Classification of Pesticides shall be applied only by a licensed professional. All pesticide applications must be in accordance with current state and federal laws and the product label. Applying pesticides within buildings using area fog dispersal methods or as warranted under DPH Rule-.20(4)(c) is restricted to licensed pest control professionals as part of an integrated pest management program

34 - grounds, walkways, porches and hallways maintained; drives provide unobstructed width and proper spacing; graded to drain; trailer spaces marked clearly, areas clean and maintained in good repair

Regulation: 511-6-2-.18(4) - trailer spacing

3 ptsCorrected: NoRepeat: No

OBSERVED TRAILER SPACES NOT MARKED CLEARLY. CA: LABEL ALL TRAILER SITES

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

OBSERVED MENS/WOMENS RESTROOM IN DISREPAIR. OBSERVED MULTIPLE TOILETS, SHOWERS, AND SINKS IN DISREPAIR. OBSERVED MISSING CEILING TILES. OBSERVED POSSIBLE BEE/WASP INFESTATION IN CEILING IN WOMENS RESTROOM. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair. While being used by tourists, every surface of a bathtub, shower, shower enclosure, toilet and lavatory, which may come in contact with a person’s body, must be sanitized each day, unless the guest has declined regular tourist room services. If a tourist declines regular tourist room services, the tourist accommodation facility must ensure that these surfaces are cleaned and sanitized at least once per week and between tourists

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

OBSERVED VENTS NOT OPERATIONAL IN RESTROOMS. OBSERVED MOLD, MILDEW, AND ODORS IN MENS/WOMENS RESTROOMS. CA: Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(9) - toilet tissue available

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Unused, individually wrapped soap or liquid soap dispensed from approved containers shall be provided in guest rooms. Soap furnished in public washrooms or baths shall be dispensed from approved containers designed to preclude contamination of the contents by individual contact.

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Toilet tissue shall be provided in a dispenser at each toilet at all times

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(7) - soap available/dispensed

2 ptsCorrected: NoRepeat: No

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Unused, individually wrapped soap or liquid soap dispensed from approved containers shall be provided in guest rooms. Soap furnished in public washrooms or baths shall be dispensed from approved containers designed to preclude contamination of the contents by individual contact

31 - barrier adequate, gate locked, and installed properly; warning sign posted, procedures and log maintained

Regulation: 511-6-2-.16(2) - swimming pool barrier

2 ptsCorrected: NoRepeat: No

OBSERVED BARRIER NOT IN A SOUND CONDITION. CA: If a swimming pool or spa at a bed and breakfast inn cannot comply with applicable regulations, then it must be enclosed with a fence at least four feet in height with a locked gate and used only by family members. In such case, guests shall not be allowed to use swimming pool or spa

35 - electrical work and materials in compliance; grounded and weatherproof outlets, properly located power lines

Regulation: 511-6-2-.18(6) - eletrical supply

1 ptsCorrected: NoRepeat: No

OBSERVED MANY BROKEN/DAMAGED ELECTRICAL BOXES. CA: Grounded and weather-proof electrical outlets supplying at least one-hundred- fifteen volts shall be provided at each trailer space. Power lines shall be located underground or suspended at least eighteen feet above ground. All electrical work and materials shall comply with the applicable International Electrical Code with Georgia Amendments and local laws, ordinances, or regulations

19 - anti-slip tubs/showers, slip strips, mats or appliqué products provided and in good condition

Regulation: 511-6-2-.08(10) - anti-slip surface

1 ptsCorrected: NoRepeat: No

OBSERVED NO ANTI SLIP MATS IN MENS/WOMENS RESTROOMS. CA: Anti-slip tubs slip strips, appliqués, or slip-proof mats shall be provided in each bathing facility and shall be kept clean and in good repair

30 - complies with all applicable regulations, permitted, approved operation

Regulation: 511-6-2-.16(1) - swimming pool in compliance with rules

1 ptsCorrected: NoRepeat: No

OBSERVED POOL NOT IN COMPLIANCE. CA: BRING POOL INTO COMPLIANCE OR DECOMMISSION POOL PERMANENTLY

Nov 21, 2023

Routine

Score: 858 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

OBSERVED NO HOT WATER IN MAIN(CENTRAL) BATHROOM FACILITY. CA: Hot and cold running water under pressure shall be provided to all lavatories and bathing facilities

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: Yes

OBSERVED MAIN(CENTRAL) BATHROOM IN NEED OF REPAIR. OBSERVED TOILETS AND URINALS IN DISREPAIR. CA: Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be constructed of easily cleanable nonabsorbent materials and shall be kept clean and in good repair. While being used by tourists, every surface of a bathtub, shower, shower enclosure, toilet and lavatory, which may come in contact with a person’s body, must be sanitized each day

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(9) - toilet tissue available

2 ptsCorrected: NoRepeat: Yes

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Toilet tissue shall be provided in a dispenser at each toilet at all times

18 - toilet tissue and soap provided; soap individually wrapped or properly dispensed

Regulation: 511-6-2-.08(7) - soap available/dispensed

2 ptsCorrected: NoRepeat: Yes

OBSERVED BATHROOMS WITH NO SOAP, TOILET PAPER, AND/OR DISPOSABLE PAPER TOWELS (OR OTHER DRYING MECHANISMS). CA: Unused, individually wrapped soap or liquid soap dispensed from approved containers shall be provided in guest rooms. Soap furnished in public washrooms or baths shall be dispensed from approved containers designed to preclude contamination of the contents by individual contact

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

OBSERVED IN MAIN(CENTRAL) BATHROOM IN NEED OF REPAIR. OBSERVED MISSING DRAIN COVERS, CEILING TILES, LIGHT COVERS, AND KNOBS FOR SINK FIXTURES. OBSERVED TOILETS/URINALS, AND SHOWERS IN DISREPAIR. CA: Floors, walls, ceilings. windows, doors and all other appurtenances shall be of sound construction, properly maintained in good repair and shall be kept clean

31 - barrier adequate, gate locked, and installed properly; warning sign posted, procedures and log maintained

Regulation: 511-6-2-.16(2) - swimming pool barrier

2 ptsCorrected: NoRepeat: No

OBSERVED GATE AROUND SWIMMING POOL IN DISREPAIR. CA: GATE AROUND SWIMMING POOL MUST BE REPAIRED

30 - complies with all applicable regulations, permitted, approved operation

Regulation: 511-6-2-.16(1) - swimming pool in compliance with rules

1 ptsCorrected: NoRepeat: No

OBSERVED SWIMMING POOL NOT FILLED IN. CA: SWIMMING POOL MUST BE FILLED IN IF THE POOL WILL NOT BE IN USE

35 - electrical work and materials in compliance; grounded and weatherproof outlets, properly located power lines

Regulation: 511-6-2-.18(6) - eletrical supply

1 ptsCorrected: NoRepeat: No

OBSERVED SEVERAL WEATHERPROOF OUTLETS NEEDING COVERS AND IN DISREPAIR. CA: OUTLETS NEED TO BE REPAIRED OR REPLACED WITH OUTLET COVERS. All electrical work and materials shall comply with the applicable International Electrical Code with Georgia Amendments and local laws, ordinances, or regulations