Permit/Opening
36 - daily recordkeeping: water testing and self inspection performed
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
The documentation provided does not indicate a daily safety self check is performed. A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
37 - other violations of the chapter
13(2)(b): The gas fired inspection for the pool heater is not available for review. For all heated pools a gas fired inspection must be completed annually. Insurance company performs gas fired inspections and CPO indicates the facility has notified the insurance company that the inspection is required on the pool heater.
37 - other violations of the chapter
.17 (4): The cyanuric acid exceeds the maximum allowance of 90 ppm. Add fresh water to pool to lower CYA amounts to a level below 90ppm.