May 5, 2026
Permit/Opening
15 - depth and no diving markers, step marking; installed and contrasting
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Depth markers are not present on tile. The markers are painted on in black paint. ". Depth markers number and letters shall be tile and four inches minimum in height. Numbers shall be of contrasting color to the background on which they are applied. Correct prior to permitting season 2028
22 - signs: peak occupancy/pool/spa/signs legible and in clearview
Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
The words No Diving are not permanent in nature on the pool deck; painted on. There is no universal symbol for No diving present. The words "No Diving" and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers. Correct prior to permitting 2028.
37 - other violations of the chapter
.17(2) The alkalinity does not meet minimum requirements. Alkalinity is required to be at 60ppm minimum and 180 ppm maximum. Speak with CPO about adjusting the alkalinity in the pool, then verify the pH is within proper range.
37 - other violations of the chapter
.17(2): The is insufficient calcium hardness in the pool. hardness is required to be at 150 ppm minimum and 1000 ppm maximum. Speak with CPO about adjusting calcium in the pool.