Mar 3, 2026
Permit/Opening
2 - self-closing / self-latching gates
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
The glass doors entering into the pool from the gym floor do not have the locking mechanisms at least 54" from the floor. The entry into the pool area from the locker rooms opens into the pool enclosure and is a push to open. The barrier door must open away from the pool and the locking mechanism must meet the minimum requirements. The facility must have corrected prior to next routine inspection. Access gates shall also comply with the requirements of this Rule and shall be equipped to accommodate a locking device. Barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. Pedestrian access gates shall be self-closing and have a self-latching device. Gates other than pedestrian access gates shall have a self-latching device. Where the release mechanism of the self latching device is located less than fifty-four inches from the bottom of the gate, 1. The release mechanism shall be located on the pool side of the gate at least three inches below the top of the gate and 2. Any openings in the gate or barrier located within eighteen inches of the release mechanism shall be less than one-half inch. 3. Mechanisms controlled by an access card reader, key entry device or keypad shall be located on the outside of the access gate.
22 - signs: peak occupancy/pool/spa/signs legible and in clearview
Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
The words "No Diving" are not present on the deck next to the depth markers. The words "No Diving" and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers. Facility has to be in compliance prior to permitting season 2028.
37 - other violations of the chapter
.13(2)(b): There is no documentation to verify the annual gas fired inspection has been performed. An annual gas fired inspections shall be performed by a qualified professional.