Sep 11, 2025
Re-inspection
28 - flow meter: appropriate range and location
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter reads at ~90 GPM at time of inspection. Ideal flow rate for this pool is ~148 GPM. Ideal flow rate can be determined by dividing the volume of the pool (gallons) by the required turnover (hour(s)) and divided by 60 minutes in an hour (minutes) = Gallons Per Minute (GPM). Corrective action: the flow meter must show accurately within +/-10% of actual flow.
17 - skimmers/gutters maintained and operable
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Inspector observed all skimmers missing weir. Corrective action: Each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.