Jekyll Island, Glynn County

Hampton Inn & Suites Spa

200 S BEACHVIEW BLVD JEKYLL ISLAND, GA 31527

Pool
Latest score
91
Mar 19, 2026
City
Jekyll Island
County
Glynn
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 19, 2026

Permit/Opening

Score: 912 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed a combined chlorine level above 0.4ppm at the time of this inspection. CA: Lower combined chlorine level to 0.4ppm or lower.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed a CYA level greater than 90ppm at the time of this inspection. CA: Lower CYA level to 90ppm or lower.

Aug 26, 2025

Routine

Score: 951 violation

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed a combined chlorine level above 0.4ppm at the time of this inspection. CA: Lower combined chlorine level to 0.4ppm or lower.

Feb 21, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Aug 14, 2024

Routine

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed a CYA level greater than 90ppm at the time of this inspection. CA: Lower CYA level to 90ppm or lower.

Apr 22, 2024

Permit/Opening

Score: 844 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed a combined chlorine level above 0.4ppm at the time of this inspection. CA: Lower combined chlorine level to 0.4ppm or lower.

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Observed insufficient turnover rate in the spa at the time of this inspection. CA: Increase the flow rate of the spa pump/filter to achieve an adequate turnover rate of 30 minutes.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed a CYA level greater than 90ppm at the time of this inspection. CA: Lower CYA level to 90ppm or lower.

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed a small gap in the surfacing of the spa and a submerged light pulled from the spa wall at the time of this inspection. CA: Repair spa surfacing and lighting fixtures to ensure there are not gaps in the spa surfacing.

Sep 29, 2023

Routine

Score: 855 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed gate not closing properly and efficiently at the time of this inspection. CA: Repair gate so it can automatically close and latch.

4 - water clarity: main drains clearly visible

Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e

15 ptsCorrected: NoRepeat: No

Observed water with a cloudy appearance preventing the bottom from being clearly seen at the time of this inspection. CA: Ensure water is clear enough to see the bottom clearly.

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed high level of chlorine at the time of this inspection. CA: Ensure chlorine level is 2.0-10.0ppm.

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

Observed a high pH level at the time of this inspection. CA: Ensure pH level remains at a 7.2-7.8.

9 - filter: approved, maintained and operating

Regulation: 511-3-5-.23(5)(c ) - (c) the pump, automatic disinfectant equipment, or other equipment necessary for continuous filtration and disinfection of the swimming pool, spa, or recreational water park attraction is not working or is unable to maintain adequate turnover rate.

15 ptsCorrected: NoRepeat: No

Observed sand leaking from the filter into the pool at the time of this inspection. CA: Facility will have the filter serviced by a pool professional and will send proof of maintenance to Glynn EH before the SPA and Kiddy Pool can be re-opened.

Aug 14, 2023

Permit/Opening

Score: 903 violations

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed flow meter missing at the time of this inspection. CA: Ensure non electrical flow meter is installed in order to view turn over rate at all times.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Observed facility PIC not testing twice daily and maintaining recorded logsheet since May 2023. CA: PIC will physically test twice daily and document values and any chemical adjustments made.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Observed facility PIC not testing twice daily and maintaining recorded logsheet since May 2023. CA: PIC will physically test twice daily and document values and any chemical adjustments made.