SAINT SIMONS ISLAND, Glynn County

Plantation Point Condominiums (Pool)

1200 PLANTATION POINT DR SAINT SIMONS ISLAND, GA 31522

Pool
Latest score
100
Apr 1, 2026
City
SAINT SIMONS ISLAND
County
Glynn
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Apr 1, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Oct 3, 2025

Routine

Score: 863 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Combined Chlorine above 0.4ppm at the time of this inspection. CA: Lower

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Turn over to meet every 6 hour should be 136gpm for flow rate. Current flow is 85. Ensure pool is meeting 6 hour flow rate requirement.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed high CYA levels at the time of this inspection. CA: Lower CYA to 90 ppm or less.

Apr 14, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Mar 26, 2025

Permit/Opening

Score: 852 violations

3 - compliant drain covers secure, present and no cracks

Regulation: 511-3-5-.23(5)(f) - (f) broken, unsecured, or missing main drain, or any submerged suction outlet cover/grate

15 ptsCorrected: NoRepeat: No

Observed pool main drain cover unsecured at the time of this inspection. CA: Main drain cover must be secured at all times during operation.

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Observed emergency phone non-operational at the time of this inspection. CA: Repair/replace emergency phone.

Nov 5, 2024

Routine

Score: 1000 violations
No violations recorded for this inspection.

Apr 12, 2024

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Oct 5, 2023

Routine

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed high CYA levels at the time of this inspection. CA: Lower CYA to 90 ppm or less.