Permit/Opening
28 - flow meter: appropriate range and location
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not reading flow at the time of this inspection CA: Repair/replace flow meter.
21 - cyanuric acid level not exceeding maximum
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed a high CYA level at the time of this inspection. CA: Lower CYA level to 90ppm or less