Jun 12, 2026
Routine
37 - other violations of the chapter
Observed Total Alkalinity at 40 ppm. C/A - adjust Total Alkalinity to at least 60 ppm. 511-3-5.22(12)
3157 DAMASCUS RD AUGUSTA, GA 30904
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
Observed Total Alkalinity at 40 ppm. C/A - adjust Total Alkalinity to at least 60 ppm. 511-3-5.22(12)
Permit/Opening
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed loose handrails around pool. C/A - tighten handrails.
Observed total alkalinity at 50 ppm. C/A - adjust total alkalinity to between 60 and 180 ppm. 511-3-5.22(9)
Re-inspection
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed 911 phone not working. C/A - Repair before reopening.
Routine
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed loose handrails on pool. C/A - tighten rails to prevent falls.
Routine
Permit/Opening
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed loose ladders on pool C/A - tighten ladders ASAP
Regulation: 511-3-5-.19(1)(b) - (b) dressing facilities, when provided, shall be have separations for each sex with no interconnection. the rooms shall be well-lighted, drained, ventilated, and of good construction with impervious materials. they shall be developed and planned so t
Observed missing fixture on Men's shower. Repair ASAP
Routine
Permit/Opening
The pressure gauge is broken.
Routine
Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.
The pressure gauge is broken.
Routine
Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.
The pressure gauge is broken.