Experiment, Spalding County

Country Inn & Suites POOL -OMNS Lodging LLC

1900 N EXPRESSWAY GRIFFIN, GA 30223

Pool
Latest score
98
Mar 12, 2026
City
Experiment
County
Spalding
Inspections
8

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 12, 2026

Re-inspection

Score: 984 violations

34 - inspection report placed in public view

Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

1 ptsCorrected: NoRepeat: No

Observed most recent routine inspection of 61 is not posted in public view. Facility has wrong inspection of 78 posted.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

.17(2) Observed that a fecal response clean-up plan is not provided.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

.17(2) Observed Total Alkalinity is low. Total Alkalinity should be between 60-180ppm.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed Calcium Hardness is low. Calcium Hardness should be between 150-1000ppm.

Dec 10, 2025

Routine

Score: 6110 violations

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed pH of pool is to0 low. The pH must not drop below 7.2ppm or go above 7.8ppm.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed combined chlorine levels are above 0.4ppm.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

Observed in log book for daily testing of chemicals that testing is not performed daily.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs are not provided at all skimmers.

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Observed current pool operator certificate is not provided.

35 - operator facility inspections performed; written documentation

Regulation: 511-3-5-.22(5) - (5) the trained operator must perform a minimum of two visits weekly and be able to provide assistance whenever needed.

4 ptsCorrected: NoRepeat: No

Observed trained pool operator is not performing a minimum of (2) visits per week based on lack of provided paperwork.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed paper towels are not provided in restroom in pool enclosure.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed toilet paper is not provided in restroom in pool enclosure.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed Total Alkalinity is low. Total Alkalinity should be between 60-180ppm.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.22(13) Observed that a fecal response clean-up plan is not provided.

Jun 16, 2025

Routine

Score: 789 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: Yes

Observed combined chlorine levels are above 0.4ppm.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed flow meter is not functioning and flow rate of pool cannot be verified.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

Observed in log book for daily testing of chemicals that testing is not performed daily.

35 - operator facility inspections performed; written documentation

Regulation: 511-3-5-.22(5) - (5) the trained operator must perform a minimum of two visits weekly and be able to provide assistance whenever needed.

4 ptsCorrected: NoRepeat: No

Observed a trained pool operator is not performing a minimum of (2) visits per week based on provided paperwork in binder.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed soap is not readily available in restroom in pool enclosure.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed paper towels are not readily available in restroom in pool enclosure.

34 - inspection report placed in public view

Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

1 ptsCorrected: NoRepeat: No

Observed inspection report is not posted in public view.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.22(13) Observed that a fecal response clean-up plan is not provided.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed Total Alkalinity is low. Total Alkalinity should be between 60-180ppm.

Dec 20, 2024

Re-inspection

Score: 934 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed combined chlorine levels are above 0.4ppm.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed toilet paper is not readily available in restroom in pool enclosure.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed Calcium Hardness is low. Calcium Hardness should be between 150-1000ppm.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed total alkalinity is low. Total alkalinity should be between 60-180ppm.

Nov 26, 2024

Routine

Score: 759 violations

14 - vacuum line protected

Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.

5 ptsCorrected: NoRepeat: Yes

Observed vacuum line on pool wall is not protected.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: Yes

Observed the combined chlorine levels are above 0.4ppm.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: Yes

Observed in log book for daily testing of chemicals that testing is not performed daily.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: Yes

Observed weirs are not provided in each skimmer.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(g) - (g) the skimmer equalizer lines shall be protected by an approved cover/grated with a flow rating equal the maximum system flow divided by the number of skimmers in the system or the maximum flow rating of the skimmer, whichever is greater.

4 ptsCorrected: NoRepeat: Yes

Observed equalizer check valve is not covered in skimmers.

35 - operator facility inspections performed; written documentation

Regulation: 511-3-5-.22(5) - (5) the trained operator must perform a minimum of two visits weekly and be able to provide assistance whenever needed.

4 ptsCorrected: NoRepeat: No

Observed documentation that the trained pool operator is performing inspections twice weekly is not provided.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed soap is not readily available at hand sink in restroom in pool enclosure.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed toilet paper is not readily available in restroom in pool enclosure.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

.17(2) Observed that the Calcium Hardness is low. Calcium Hardness should be between 150-1000ppm.

Jul 3, 2024

Re-inspection

Score: 806 violations

14 - vacuum line protected

Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.

5 ptsCorrected: NoRepeat: Yes

Observed vacuum line on pool wall is not protected.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed the combined chlorine levels are above 0.4ppm.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: Yes

Observed in log book for daily testing of chemicals that testing is not performed daily.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weir is not provided in each skimmer.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

.17(2) Observed that the Calcium Hardness is low. Calcium Hardness should be between 50-1000ppm, with 200-400ppm being ideal.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

.17(2) Observed that the Alkalinity is low. Alkalinity should be between 60-180ppm.

Jun 28, 2024

Routine

Score: 758 violations

4 - water clarity: main drains clearly visible

Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e

15 ptsCorrected: NoRepeat: No

Observed water clarity is not adequate.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed the pH levels are to low. The pH range is 7.2ppm to 7.8ppm with ideal range being 7.4ppm-7.6ppm.

14 - vacuum line protected

Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.

5 ptsCorrected: NoRepeat: No

Observed vacuum line on pool wall is not protected.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Observed in log book for daily testing of chemicals that testing is not performed daily.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weir is not provided in each skimmer.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.16(7) Observed test kit is not provided for the monitoring of pool chemicals.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17(2) Observed that the Calcium Hardness is low. Calcium Hardness should be between 150 - 1000, with the 200-400 being ideal.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17 (2) Observed that the Alkalinity is low. Alkalinity should be between 60ppm - 180ppm.

May 26, 2023

Permit/Opening

Score: 952 violations

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Observed that the Certified Pool Operator certificate is not posted or provided.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

.17 (2) Observed that the Calcium Hardness is low. Calcium Hardness should be between 150 - 1000, with the 200-400 being ideal.