Kingsland, Camden County

Arbours at Kingsland

901 S GROVE BLVD KINGSLAND, GA 31548

Pool
Latest score
96
May 7, 2026
City
Kingsland
County
Camden
Inspections
11

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 7, 2026

Re-inspection

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: Yes

At time of inspection, the cyanuric acid level registered at 101 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water, to ensure that CYA is below 90 ppm.

May 6, 2026

Re-inspection

Score: 812 violations

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

At time of inspection, the emergency phone is not functional (no sound can be heard). CPO states TDS was out yesterday evening and the phone was fixed at that time and began working. CPO has called TDS again and they are scheduled to come out today between 1:00 - 3:00 PM to troubleshoot.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

At time of inspection, the cyanuric acid level registered at 102 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water, to ensure that CYA is below 90 ppm.

May 5, 2026

Permit/Opening

Score: 851 violation

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

At time of inspection, the emergency phone is not operational (no sound is heard). CPO is contacting TDS, to have them come out to troubleshoot the phone.

May 28, 2025

Re-inspection

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

At time of inspection, the cyanuric acid level registered at 187 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water.

May 20, 2025

Re-inspection

Score: 803 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: Yes

At time of inspection, the free chlorine level is still too high (registered at 20.53 ppm - must be between 2-10 ppm). CPO is going to drain some water and add some fresh water (stabilizer is also extremely high, contributing to the consistently high chlorine levels). CPO also lowered the chlorinator setting from 2 to 1.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: Yes

At time of inspection, the cyanuric acid level is still high (registered at 259 ppm - must be 90 ppm or less). CPO is going to drain a good bit of water (to also address the high free chlorine level).

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

At time of inspection, the alkalinity has improved, but it is still below the minimum level (registered at 48 ppm, must be 60-180 ppm). CPO is working on balancing the water.

May 9, 2025

Re-inspection

Score: 803 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: Yes

At time of inspection, the free chlorine level is still too high (registered at 15.32 ppm; must be between 2 and 10 ppm). CPO will drain some water and add some fresh water.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: Yes

At time of inspection, the cyanuric acid level registered at 170 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

At time of inspection, the total alkalinity registered as zero. CPO is working on balancing the pool.

May 8, 2025

Permit/Opening

Score: 804 violations

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

At time of inspection, the emergency phone is not operational. CPO is troubleshooting.

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

At time of inspection, the free chlorine registered at 13.21 ppm (must be between 2 and 10 ppm). CPO lowered the setting on the chlorinator and will monitor the level.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

At time of inspection, the cyanuric acid level registered at 118 ppm (CYA must be 90 ppm or less). CPO will drain some water and add some fresh water.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

At time of inspection, the total alkalinity registered as zero. Total alkalinity must be between 60 and 180 ppm. CPO will adjust, while ensuring that pH stays within range.

May 23, 2024

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 22, 2024

Re-inspection

Score: 852 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: Yes

At time of inspection, the free chlorine is still low (0.85 ppm and must be at least 2.00 ppm). CPO added more chlorine tablets to the erosion feeder.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: NoRepeat: No

At time of inspection, the pH registered at 7.0 (pH must be between 7.2 and 7.8). CPO will adjust.

May 21, 2024

Re-inspection

Score: 802 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: Yes

At time of inspection, the free chlorine registered at 0.66 ppm (free chlorine for this pool must be at least 2.00 ppm). CPO discovered that the chlorinator had been turned down - CPO increased the chlorinator output.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

At time of inspection, observed the combined chlorine (CC) at 0.92 ppm - CPO will drain some water and add some fresh water.

May 20, 2024

Permit/Opening

Score: 851 violation

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

At time of inspection, free chlorine registered at 0.15 ppm (free chlorine must be at least 2.00 ppm for this pool). CPO will adjust and re-inspection performed tomorrow (5/21/2024).