Jun 8, 2026
Permit/Opening
301 NOBLE OAKS DR SAVANNAH, GA 31406
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Obsereved flow greater than what the flow meter can read. PIC stated that he ordered a new one.
RCA: The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate.
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine reading of 15ppm, exceeding maximum disinfectant levels.
RCA: Free Chlorine level in pools using cyanuric acid or a stabilized chlorine product; Minimum 2.0 Ideal 2.0-5.0 Maximum 10.0
Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.
Observed combined chlorine exceeding 0.4ppm maximum.
RCA: Cyanuric acid shall not exceed 0.4ppm.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter bobber stuck and unable to indicate flow levels.
RCA: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
Regulation: 511-3-5-.18(2) - (2) rope and float line. a rope and float line shall be provided within one foot of and on the shallow side of the break in grade between the shallow and deep portions of the swimming pool, with its position marked with visible floats at intervals of
Observed no float line in pool. CPO stated it was popped a few weeks ago by patrons and they are waiting on a new one.
RCA: A rope and float line shall be provided within one foot of and on the shallow side of the break in grade between the shallow and deep portions of the swimming pool, with its position marked with visible floats at intervals of seven feet or less.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed cyanuric acid reading of HI on ColorQ.
RCA: Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90
Observed calcium hardness reading of LOW on ColorQ. Taylor kit testing did not change to allow for detection of chemical levels.
RCA: Calcium hardness shall be a minimum of 150ppm and shall not exceed 1000ppm.