REX, Clayton County

Rex Child Care

6359 HWY. 42 REX, GA 30273

Pool
Latest score
98
Jul 15, 2025
City
REX
County
Clayton
Inspections
2

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jul 15, 2025

Re-inspection

Score: 981 violation

12 - grab/hand rails, ladders installed and secure

Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

2 ptsCorrected: YesRepeat: No

Observed pool entry steps without markers. Advised PIC the outer two inches of each step shall be marked with slip resistant tiles in a contrasting color. PIC sent email stating he will have markers placed by 7/16/25 evening.

Jul 7, 2025

Permit/Opening

Score: 629 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: YesRepeat: No

Observed the self-closing latch not working properly. Advised PIC the latch shall be working at all times. COS: Latch was repaired.

11 - appropriate lifesaving equipment present

Regulation: 511-3-5-.23(5)(h) - (h) absence of required lifesaving equipment on the deck or an emergency phone;

15 ptsCorrected: YesRepeat: No

Lifesaving equipment not present during inspection. COS: CPO obtained lifesaving equipment.

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Unable to determine adequate turnover rate due to flow meter inoperable. Advised PIC adequate turnover rate shall be verified during inspections.

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

Observed flow meter improperly functioning during inspection, unable to determine reading of flow rate. Advised PIC the flow meter shall be properly working.

15 - depth and no diving markers, step marking; installed and contrasting

Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.

4 ptsCorrected: NoRepeat: No

Observed universal no diving markers around pool deck. Advised PIC the pool deck shall indicate no diving markers.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed missing weirs from the skinner baskets. Advised PIC weirs shall be present at all times.

12 - grab/hand rails, ladders installed and secure

Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

2 ptsCorrected: NoRepeat: No

Observed pool entry steps without markers. Advised PIC the outer two inches of each step shall be marked with slip resistant tiles in a contrasting color.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: No

Observed the maximum occupancy sign and pool hours not posted during time of inspection. Advised PIC the maximum occupancy sign and pool hours shall be present at all times. Advised to obtain appropriate signage.

24 - piping identified and marked

Regulation: 511-3-5-.08(6) - (6) all piping shall be marked with directional arrows as necessary to determine flow direction. all piping in the equipment room shall be permanently identified by its use and the pool and or aquatic feature it serves.

1 ptsCorrected: YesRepeat: No

Observed piping markers missing form pipes. Advised PIC pipes shall be re-identified at all times. COS: Piping was identified.