RIVERDALE, Clayton County

Belmont Crossing Apartment Homes

269 HIGHWAY 138 RIVERDALE, GA 30274

Pool
Latest score
100
Jun 26, 2025
City
RIVERDALE
County
Clayton
Inspections
5

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 26, 2025

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 14, 2025

Permit/Opening

Score: 649 violations

1 - barrier: pool enclosed/fencing in compliance

Regulation: 511-3-5-.18(11)(b) - (b) openings in the barrier shall not allow passage of a four inch diameter sphere.

15 ptsCorrected: NoRepeat: No

Observed gap in fence. Advised PIC openings cannot exceed greater than 4 inches. Advised to repair.

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Emergency phone inoperable. Advised PIC emergency phone shall be working. Advised to repair.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: NoRepeat: No

Observed pH reading 8 ppm. Advised PIC pH levels shall read between 7.2-7.8 ppm. Advised to adjust pH.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Flow meter not meeting required gpm to meet 6 hr turnover. Advised to adjust.

15 - depth and no diving markers, step marking; installed and contrasting

Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.

4 ptsCorrected: NoRepeat: No

Observed no universal no diving symbol. Advised PIC to install universal no diving applique. Advised at time of renovation (resurface of pool or deck) permanent tile shall be installed.

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed missing weirs. Advised to install weirs.

20 - return inlets maintained

Regulation: 511-3-5-.10(1)(a) - (a) pools shall use wall or floor inlets that are adequate in design, number and location to provide adequate mixing.

4 ptsCorrected: NoRepeat: Yes

Observed missing inlet cover. Advised PIC to replace.

16 - pool deck: maintained, unobstructed and clean

2 ptsCorrected: NoRepeat: No

Observed broken tile @ pool. Advised to repair.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: Yes

Observed missing pool occupancy sign. Advised to install.

May 30, 2024

Permit/Opening

Score: 942 violations

20 - return inlets maintained

Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.

4 ptsCorrected: NoRepeat: No

Upon arrival, observed missing return inlet cover. Advised CPO that return inlets shall not constitute a hazard to the user. Advised to place a return inlet cover.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed 'NO DIVING' tiling less that 4-inch lettering. Also observed no universal no diving symbol tile marker not installed at each depth marker. Advised CPO The words "No Diving" and the universal international symbol for “NO DIVING” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that outlined for depth markers. Advised CPO to install 'NO DIVING' marker in at least 4-inch lettering in contrasting color and to install universal no diving symbol tile marker on the pool deck.

Jun 1, 2023

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 24, 2023

Permit/Opening

Score: 785 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed gate/fenching not self closing/self latching. Advised to repair

20 - return inlets maintained

Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.

4 ptsCorrected: NoRepeat: No

Observed 1 return inlet cover missing. Advised to cover

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.

2 ptsCorrected: NoRepeat: No

Observed no maximum occupancy sign posted. Advised to post

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou

2 ptsCorrected: NoRepeat: No

Observed no universal no diving symbol. Advised to obtain and place on deck

24 - piping identified and marked

Regulation: 511-3-5-.08(6) - (6) all piping shall be marked with directional arrows as necessary to determine flow direction. all piping in the equipment room shall be permanently identified by its use and the pool and or aquatic feature it serves.

1 ptsCorrected: NoRepeat: No

Observed piping in pump room with directional flow not marked. Advised to mark pipes