Newnan, Coweta County

Westhill Newnan Crossing

285 SUMMERLIN BLVD NEWNAN, GA 30265

Pool
Latest score
94
Jun 8, 2026
City
Newnan
County
Coweta
Inspections
11

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 8, 2026

Permit/Opening

Score: 942 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Turnover could not be determined due to broken flow meter.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed several tiles missing from one interior pool wall. Swimming pools and spas and their appurtenances shall be constructed of materials which are nontoxic to man and the environment, impervious and enduring, able to withstand design stresses, and able to provide a watertight structure with a smooth and easily cleaned surface without cracks or joints, excluding structural joints, or to which a smooth, easily cleaned surface finish is applied or attached.

Jun 11, 2025

Re-inspection

Score: 991 violation

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: Yes

Pool deck shower not operational. Part has been ordered.

Jun 10, 2025

Re-inspection

Score: 793 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed chlorine measuring above maximum concentration at 12.5.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: Yes

Water is not being tested twice daily, nor on weekends, and records have not been maintained.

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(18) - (18) class c multi-family residential housing pools are exempt from the requirements of (17) and (18) of the rule, if the facility is only open to residents and their guests.

1 ptsCorrected: NoRepeat: Yes

Pool deck shower not operational. Part has been ordered.

Jun 6, 2025

Routine

Score: 843 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed one of the gates was not self-locking during inspection.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: NoRepeat: No

Observed pH measuring high above the maximum of 7.8.

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: Yes

Pool deck shower not operational.

Apr 14, 2025

Permit/Opening

Score: 991 violation

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: Yes

Pool deck shower not operational.

Jul 12, 2024

Routine

Score: 884 violations

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: YesRepeat: No

Observed flow meter reading at 0gpm. Flow meter restored to proper function during inspection (120gpm).

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

No daily records kept on location.

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: Yes

Pool deck shower not operational.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

Observed total alkalinity below minimum level of 60ppm.

May 17, 2024

Re-inspection

Score: 982 violations

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: No

Pool deck shower not operational.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed total alkalinity below minimum level of 60, and calcium hardness below minimum level of 150.

May 15, 2024

Re-inspection

Score: 803 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed chlorine above maximum.

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Facility did not have a CPO certificate.

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: No

Pool deck shower not operational.

May 13, 2024

Permit/Opening

Score: 735 violations

8 - chemical feeder operational and approved

Regulation: 511-3-5-.23(5)(c ) - (c) the pump, automatic disinfectant equipment, or other equipment necessary for continuous filtration and disinfection of the swimming pool, spa, or recreational water park attraction is not working or is unable to maintain adequate turnover rate.

15 ptsCorrected: NoRepeat: No

Observed chlorine tablets in the skimmer, could not verify equipment working.

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

For adequate turnover rate, flow meter should read 63 GPM or higher. Flow meter was at 0 GPM.

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Facility did not have CPO certificates for people completing tests/visits.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

Regulation: 511-3-5-.18(12)(b) - (b) where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “warning - no life guard on duty and risk of drowning - supervis

2 ptsCorrected: NoRepeat: No

No lifeguard sign posted.

30 - deck/rinse shower maintained

Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.

1 ptsCorrected: NoRepeat: No

Pool deck shower not operational.

Aug 16, 2023

Routine

Score: 863 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: Yes

For adequate turnover rate, flow meter should read 63 GPM or higher. Flow meter was at 20 GPM.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

Not testing twice daily, everyday.

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

Facility did not have CPO certificates for people completing tests/visits.

Jun 13, 2023

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

For adequate turnover rate, flow meter should read 63 GPM or higher. Flow meter was at 50 GPM.