Nov 6, 2025
Re-inspection
18 - combined chlorine level 0.4 ppm or less
Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.
Combined chlorine shall not exceed 0.4 ppm. Reading today was over 0.4 ppm. Informed the CPO. Gave documentation on how to correct it.
19 - adequate turnover rate
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Flow meter shall read a minimum of 182 gpm for a 30 minute turnover rate. Todays reading was 130 gpm. Informed the CPO and he adjusted accordingly.
37 - other violations of the chapter
511-3-5-.17 The calcium harness level reading was 100 ppm. The value should not fall below 150 ppm. Informed CPO.