ATLANTA, DeKalb County

INDIGO APARTMENTS

2515 NORTHEAST EXPY ATLANTA, GA 30345

Pool
Latest score
95
May 19, 2026
City
ATLANTA
County
DeKalb
Inspections
4

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 19, 2026

Re-inspection

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

Observed low turnover rate of 45gpm (36,000 gallon pool should have a minimum of 100gpm turnover rate).

13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain the minimum required number of four (4) turnovers per day, or one turnover every six (6) hours. All pool piping systems shall be designed to accommodate one hundred percent (100%) of the design flow rate.

May 13, 2026

Permit/Opening

Score: 803 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed low FCL concentration levels measuring at 1.00ppm.

13-189(c)(1): Where stabilizing agents are used, a free-chlorine residual shall be maintained at a concentration of no less than three parts per million (3ppm) at all times. The maximum stabilized or unstabilized free chlorine residual shall not exceed ten parts per million (10ppm).

PIC will reschedule once FCL is within range.

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

Observed high pH levels measuring at 7.9ppm.

13-189(c)(1): The pool shall be maintained in an alkaline condition at all times with a pH level between 7.2 – 7.8.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

Observed low turnover rate of 65gpm (36,000 gallon pool should have a minimum of 100gpm turnover rate).

13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain the minimum required number of four (4) turnovers per day, or one turnover every six (6) hours. All pool piping systems shall be designed to accommodate one hundred percent (100%) of the design flow rate.

May 30, 2025

Re-inspection

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

Observed low turnover rate of 60gpm (36,000 gallon pool should have a minimum of 100gpm turnover rate).

13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain the minimum required number of four (4) turnovers per day, or one turnover every six (6) hours. All pool piping systems shall be designed to accommodate one hundred percent (100%) of the design flow rate.

May 28, 2025

Permit/Opening

Score: 803 violations

4 - water clarity: main drains clearly visible

15 ptsCorrected: NoRepeat: No

Water observed was cloudy and main drains on the bottom of the pool at the deepest point were not clearly visible from the deck. Drain type, shape and number of openings of the main grates could not be clearly distinguished.

13-189(c)(6): At all times when a pool is in use, the water shall be of such clarity that the main drains on the bottom of the pool at the deepest point are clearly visible from the deck. The viewer shall be able to clearly distinguish the type, shape and number of openings of the main drain grates or covers.

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed low FCL concentration levels measuring at 1.88

13-189(c)(1): Where stabilizing agents are used, a free-chlorine residual shall be maintained at a concentration of no less than three parts per million (3ppm) at all times. The maximum stabilized or unstabilized free chlorine residual shall not exceed ten parts per million (10ppm).

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

Observed low turnover rate of 70gpm (36,000 gallon pool should have a minimum of 100gpm turnover rate).

13-190(a): The equipment shall be operated continuously on a twenty-four (24) hour basis to obtain the minimum required number of four (4) turnovers per day, or one turnover every six (6) hours. All pool piping systems shall be designed to accommodate one hundred percent (100%) of the design flow rate.