Jun 9, 2026
Permit/Opening
28 - flow meter: appropriate range and location
13-190(a)(7): An adequately sized flow meter shall be installed on the return line. Observed flow meter not installed on the return line.
3692 ASHFORD-DUNWOODY RD ATLANTA, GA 30319
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-190(a)(7): An adequately sized flow meter shall be installed on the return line. Observed flow meter not installed on the return line.
Permit/Opening
Routine
Permit/Opening
Routine
13-189(c)(1): the free chlorine residual in all parts of the pool must be between 1.5ppm-10.0ppm. It was recorded twice at 0.45ppm & 0.54ppm. It was COS to 2.33
13-190(a): Equipment shall be operated continuously on a 24 hour basis to obtain minimum required turnover of 1 turnover every 6 hours. Observed the flow rate at 280 and it should be reading at 347.
Routine
13-190(a): Equipment shall be operated continuously on a 24 hour basis to obtain minimum required turnover of 1 turnover every 6 hours. Observation: Flow meter read 290gpm. After back washing, it increased to 320. Mininmum turnover is 347 gpm.
13-190(a)(7): An adequately sized flow meter shall be installed on return line. Observation: Flow meter max was 420. Max value must be 1.5x of turnover rate (347 gpm). Max value should be 520.5 gpm.