19 - adequate turnover rate
13-205(b)(1) equipment shall be ran to meet requirements of 4 turnovers/day. Observed: flow rate is at 60 GPM, the required flow rate is 85 GPM
600 NORTHERN AVE CLARKSTON, GA 30021
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-205(b)(1) equipment shall be ran to meet requirements of 4 turnovers/day. Observed: flow rate is at 60 GPM, the required flow rate is 85 GPM
Permit/Opening
13-202(a)(2) entry into the pool area shall be through a self-closing, self-latching gate, entrance gate must be able to self-close. Observed: gate does not close on its own
13-189(c)(6) water shall be of such clarity that the main drains on the bottom of the pool are clearly visible from the deck. Main drains are currently not visible
13-189(c)(1) free chlorine shall not exceed 10 ppm. Observed: chlorine is currently at 10.55 ppm
13-202(d) each pool shall be provided with a coast guard approved ring buoy firmly attached to rope. Observed: current rope is broken on the surrounding edge of the buoy
13-205(b)(1) equipment shall be ran to meet requirements of 4 turnovers/day. Observed: flow rate is at 42 GPM, the required flow rate is 85 GPM
Permit/Opening
13-205(b)(1) Turnover rate should be 6 hours or lower. Pool's current turnover rate is 8 hours
Routine
13-202(c): pool operators shall keep a log of daily pH and chlorine levels as well as actions to maintain chemicals in range.
Permit/Opening
Permit/Opening
13-189(c)(6); At all times when a pool is in use, the water shall be of such clarity that the main drains on the bottom of the pool at the deepest point are clearly visible from the deck. Observed the entire pool water to be cloudy.
13-189(c)(1): The pool shall be maintained in an alkaline condition at all times with a pH level between 7.2-7.8. Observed pH level at 8.3.
Permit/Opening
13-190(a)(7): an adequately sized flow meter shall be replaced on the return line. The flowmeter range is too high (it maxes out at 300 and reads at 140 which isn't the right turnover for this size pool). A new flowmeter needs to be placed in the appropriate range.
13-188(a): pool surface shall have no cracks or open joint. There is a crack running along the base of the pool. The surface needs to be resurfaced in the off season.