Dunwoody, DeKalb County

MILL GLEN SWIM CLUB (POOL)

5565 MILL TRACE DR DUNWOODY, GA 30338

Pool
Latest score
95
Jun 10, 2026
City
Dunwoody
County
DeKalb
Inspections
12

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 10, 2026

Routine

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Observed low turnover rate.

Apr 23, 2026

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) The equipment shall be operated continuously on a 24 hour basis to obtain the minimum required number of 6 hours turnovers per day. Observed flowmeter at 340 gpm, where the minimum should be 413 gpm for a 149,000 gal pool.

Jul 29, 2025

Routine

Score: 1000 violations
No violations recorded for this inspection.

Jun 12, 2025

Routine

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) The equipment shall be operated continuously on a 24 hour basis to obtain the minimum required number of 4 hours turnovers per day

Jun 10, 2025

Routine

Score: 764 violations

2 - self-closing / self-latching gates

15 ptsCorrected: NoRepeat: No

13-202(a)(2): Entry into the pool area shall be a self-closing, self-latching gate. Observed the gate did not close properly as the latching part was loose. Head lifeguard fixed the loose screws and corrected the issue.

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(i) No disinfectant added by hand as the sole or primary method of adding disinfectant or pH control.

33 - lifeguard training certification available onsite

5 ptsCorrected: NoRepeat: No

13-202(e): Code says lifeguard training certification must be available on site -Observed no certification

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-19(a)(4) Each skimmer shall be properly design and operating weir or other departmentally approved means of providing effective skimming.

Apr 29, 2025

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

Turnover rate observed to be a bit low (should be 458 for 165k gal pool at 6 hr turnover).

Jul 30, 2024

Routine

Score: 951 violation

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Turn overate was observed to be too low on the flowmeter.

Jul 1, 2024

Routine

Score: 1000 violations
No violations recorded for this inspection.

May 14, 2024

Permit/Opening

Score: 951 violation

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed the flow meter reading at 270 gpm. Discussed with the person in charge that flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.

Aug 23, 2023

Routine

Score: 875 violations

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

13-205(b)(1): Code says there must be one turnover every 6 hours -Flow needed: 472gpm -Flow observed: 300gpm

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: Yes

13-196(a)(4): Code says skimmers must have weirs -Observed half the weirs missing

16 - pool deck: maintained, unobstructed and clean

2 ptsCorrected: NoRepeat: No

13-188(h)(3): Code says deck surface should be in good repair -Observed tiles to come up near entrance of pool

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(k): Code says trashcans must have lids -Observed no lid in men's room

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c): Code says current inspection must be in public view. -Observed old inspection

Jul 11, 2023

Routine

Score: 763 violations

6 - proper disinfectant level

15 ptsCorrected: YesRepeat: Yes

13-189(c)(1): Code says disinfectant must be 3.0-10.0ppm -First Reading: 2.25 -Second Reading: 3.03 -COS

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: Yes

13-205(b)(1): Code says there must be one turnover every 6 hours -Flow needed: 472gpm -Flow observed: 300gpm

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4): Code says skimmers must have weirs -Observed half the weirs missing

May 31, 2023

Routine

Score: 715 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1): Code says disinfectant levels must be between 3.0 and 10.0 ppm -First Observation: 1.60 -Second Observation: 5.60 COS

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a): Code says pool must have an adequate flow rate -Flow needed: 381 gpm -Flow observed: 220 gpm

33 - lifeguard training certification available onsite

5 ptsCorrected: NoRepeat: No

13-202(e): Code says lifeguard training certification must be available on site -Observed no certification

12 - grab/hand rails, ladders installed and secure

2 ptsCorrected: NoRepeat: No

13-188(f): Code says handrails must be secured -Observed handrail to come out of place COS

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-199(d): Sign saying "only one user on diving platform at any time" must be present -Observed no sign