May 20, 2025
Permit/Opening
19 - adequate turnover rate
13-205(b)(1): Equipment shall be operated on one turnover six(6) hours (pools). Observed flowmeter at 70gpm. Pool turnover rate shall be at least 127gpm.
2700 SUMMIT CREEK DR STONE MOUNTAIN, GA 30083
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-205(b)(1): Equipment shall be operated on one turnover six(6) hours (pools). Observed flowmeter at 70gpm. Pool turnover rate shall be at least 127gpm.
Permit/Opening
Permit/Opening
13-183(d): Code defines wastewater discharge (backwashing) as lines discharging to sewer line. Obs: backwash pipe is leaking. I was notified that it spills into stagnant water/pond adjacent to equipment room. There is a lot of water outside equipment room door.
13-198(b): Ready-access ventilation shall be provided by chlorine resistant fan. Obs: No fan present. There is an opening on top of door but the vent is loose.