Apr 2, 2026
Permit/Opening
19 - adequate turnover rate
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed flow meter not showing an adequate turnover rate for required turnover.
512 FORSYTH DR HINESVILLE, GA 31313
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed flow meter not showing an adequate turnover rate for required turnover.
Re-inspection
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed flow rate of 60 gpm. Pool needs flow rate of 112 gpm for adequate turnover.
Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Observed daily water testing is not being done when CPO does not come.
Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.
Observed no soap in the restrooms.
Routine
Regulation: .17((1)(c) - proper disinfectant level
Observed free chlorine levels >10ppm.
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed turnover rate of 60 gpm. Pool needs flow rate of 112 gpm for adequate turnover.
Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Observed daily water testing is not being done when CPO does not come.
Permit/Opening
Routine
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed no flow rate on flowmeter.
Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Observed no evidence that facility is conducting chlorine and pH checks twice per day.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed weirs missing from 2 skimmers. Observed chlorine tablets in all skimmers. This may indicate an issue with the chlorinator.
511-3-5-.06(1)(y) Observed grass growing in cracks, expansion joints and drains in pool deck.
Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
Observed that current inspection report and permit are not posted