Augusta, Richmond County

AUGUSTA MARRIOTT HOTEL & SUITES OUTDOOR POOL

2 10TH ST AUGUSTA, GA 30901

Pool
Latest score
100
Mar 18, 2026
City
Augusta
County
Richmond
Inspections
11

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 18, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Dec 17, 2025

Routine

Score: 1000 violations
No violations recorded for this inspection.

Jul 28, 2025

Routine

Score: 812 violations

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: YesRepeat: No

Added soda ash to increase pH after adding water.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Reduce cyanuric acid (CYA) to below 90 ppm for chlorine to be effective.

Apr 4, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Mar 24, 2025

Permit/Opening

Score: 823 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

Unable to read due to expired reagents; DPD #2 expired 9/24.

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Repair broken deck drain cover.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Need unexpired reagents.

Jul 2, 2024

Re-inspection

Score: 851 violation

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.

15 ptsCorrected: YesRepeat: No

pH<6.8; added 2 lbs soda ash to increase pH.

Jun 27, 2024

Routine

Score: 812 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

Free chlorine must be 2.0ppm -10.0ppm during operation.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Reduce cyanuric acid (CYA) to below 90 ppm for chlorine to be effective.

Apr 1, 2024

Permit/Opening

Score: 851 violation

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: YesRepeat: No

Added 1lb. soda ash to correct pH.

Dec 18, 2023

Routine

Score: 1000 violations
No violations recorded for this inspection.

Aug 31, 2023

Routine

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type

5 ptsCorrected: NoRepeat: No

Stuck @ 40 GPM

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Cyanuric 100ppm.

Jun 1, 2023

Routine

Score: 912 violations

19 - adequate turnover rate

Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat

5 ptsCorrected: NoRepeat: No

Stuck @ 40 GPM

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Cyanuric 100ppm.