Aug 13, 2025
Re-inspection
2650 MOUNT ZION PKWY JONESBORO, GA 30236
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone not working properly at the time of inspection. Advised PIC the emergency phone shall be in good repair.
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed the ph reading at 7.0 ppm. Advised PIC ph shall read between 7.2-7.8.
Regulation: 511-3-5-.07(1)(b) - (b) turnover rates for pools by type listed below: type
Observed pool not meeting a required turnover rate of 6 hours. Advised PIC the pool shall meet the minimum turnover rate at all times.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed loose grab rail at entry steps. Advised to tighten.
Re-inspection
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine reding at 0ppm. Advised PIC the chlorine level shall measure between 3-10 ppm. COS: PPM adjusted to 7.4.
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed the ph level above 8.0. Advised PIC the ph shall measure between 7.2 and 7.8.
Regulation: 511-3-5-.23(5)(h) - (h) absence of required lifesaving equipment on the deck or an emergency phone;
Observed lifesaving rope with fraying on the ends. Advised PIC rope shall be maintained.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not working properly. Advised PIC to backwash. COS: Meter working properly.
Observed fountain not working. Advised PIC fountain shall be maintained. in good repair.
Routine
Regulation: .17((1)(c) - proper disinfectant level
Observed Cl in the pool at 0ppm. Advised to correct
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not working properly. Advised to correct
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Observed maximum occupancy not filled out. Advised to correct
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed the flow meter is incapable of reading correct flow due to range. CA: Will need to replace with flow meter that is able to indicate the range greater than 120 gpm; the flow meter should be capable of measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided
Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
Current inspection score was not posted to the public or in an approved manner. CA: Will need to post the most current inspection to the public as approved.
There is standing water in the pump room and chemicals are stored in the standing water. CA: Will need to determine the source of the water and will need to store chemicals as prescribed by manufacturer as safe storage/safe practice.
Re-inspection
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not working properly. Advised to repair
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed weir on 5ft end not working. Advised to repair
Regulation: 511-3-5-.06(1)(f) - (f) the deck, including coping, shall have a minimum four feet width of continuous, unobstructed walking area maintained at all times unless otherwise allowed in the chapter.
Observed trip hazard on deck near 5ft ladder. Advised to repair
Regulation: 511-3-5-.18(12)(a) - (a) the words "no diving" and the universal international symbol for “no diving” shall be permanently visible at the edge of the deck for water five feet in depth or less, placed only on the deck beside the depth markers, and shall conform to that ou
Observed pool with no universal No Diving symbol on deck. Advised to obtain
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Observed pool with no maximum occupancy sign. Advised to obtain
Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.
Observed deck shower not working. Advised to repair