Mableton, Cobb County

ONELIFE FITNESS AUSTELL - SPA

1025 EAST WEST CONNECTOR STE 200 AUSTELL, GA 30106-8513

Pool
Latest score
95
Mar 27, 2026
City
Mableton
County
Cobb
Inspections
9

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 27, 2026

Re-inspection

Score: 951 violation

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: Yes

No flow meter was observed.

C/A: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided.

Mar 26, 2026

Routine

Score: 794 violations

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Emergency phone not operable.

C/A: An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed pH at 8.0.

C/A: pH shall be between 7.2-7.8

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

No flow meter was observed.

C/A: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided.

34 - inspection report placed in public view

Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

1 ptsCorrected: NoRepeat: No

Most recent inspection report was not posted.

C/A: The operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.

Sep 22, 2025

Routine

Score: 1000 violations
No violations recorded for this inspection.

Jun 5, 2025

Routine

Score: 852 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed chlorine reading at 2ppm, under minimum for spas (3 ppm)

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

Observed pH at 7.0, under minimum

Jun 5, 2025

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 15, 2024

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 13, 2024

Routine

Score: 812 violations

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed pool at 7.0 pH level.

CA: Pool must be maintained at 7.2-7.8

20 - return inlets maintained

Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.

4 ptsCorrected: NoRepeat: Yes

Missing inlet cover.

CA: Covers shall be installed on return inlets.

Nov 6, 2023

Re-inspection

Score: 961 violation

20 - return inlets maintained

4 ptsCorrected: NoRepeat: No

Replace missing inlet plate

Oct 25, 2023

Permit/Opening

Score: 746 violations

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

Phone not working

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Maintain chlorine at 3-10 ppm

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

Maintain pH at 7.2 - 7.8

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

Repair or replace flow meter - float not moving

20 - return inlets maintained

4 ptsCorrected: NoRepeat: No

Replace missing inlet plate

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

Mount spa rules sign in spa area