Brookhaven, DeKalb County

THE REN AT BROOKHAVEN (SPA)

2924 CLAIRMONT RD ATLANTA, GA 30329

Pool
Latest score
98
May 22, 2026
City
Brookhaven
County
DeKalb
Inspections
2

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 22, 2026

Permit/Opening

Score: 982 violations

24 - piping identified and marked

1 ptsCorrected: YesRepeat: No

Observed pipes not labeled during time of inspection.

13-191(a) All valves and piping in the equipment rooms shall be clearly labeled, and water flow direction shall be indicated on exposed piping in the filter room.

CPO labeled pipes during inspection.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed ventilation system not functioning properly in pump room during time of inspection.

CA: 13-198(b) Ready access, suitable drainage (such as a sump pump) and ventilation of fresh make-up air must be provided for all equipment rooms. The enclosure must be ventilated with outside air by a chlorine-resistant exhaust fan with vents that are located a maximum of four inches (4”) above the floor level, equipped with automatic louvers to achieve cross-flow ventilation located at the top of the enclosure for admitting fresh air, and capable of providing one (1) enclosure air change every three (3) minutes. The exhaust fan shall be installed so as to exhaust the equipment room air away from the pool enclosure and adjacent inhabited areas. The entire enclosure shall have a concrete floor that slopes one-quarter inch per foot (¼” / 1’) to a floor drain connected to a sanitary sewer. A hose bibb with an approved backflow prevention system shall be provided in the equipment room or enclosure.

Advise CPO to repair or replacement is required to maintain adequate ventilation in the pump room.

Jun 2, 2025

Permit/Opening

Score: 951 violation

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallon per minute. Observed flow meter not functioning properly.